Lapp kabel 1270031 CABLE RE-2X(ST)Y 1x2x0.75 MM2
Chi tiết
Design
- Stranded plain annealed copper wires
- XLPE core insulation
- Pairs are collectively screened with alu-minium polyester tape
- Tinned copper drain wire
- PVC outer sheath, black or blue
Technical data
Core identification code
Pair: black and white
Multipair: black and white with numbers
Based on
EN 50288-7
Specific insulation resistance
> 1000 MOhm x km
Conductor stranding
acc. to IEC 60228 Cl. 2
Minimum bending radius
6 x cable diameter
Nominal voltage
500V
<50 VAC / <75 VDC for Intrinsically Safe (IS)
circuits application. See application range.
Test voltage
2000 V
Temperature range
-30°C to +90°C